BUSHING WELL 200 AMP 35 KV

 BUSHING WELL 200 AMP 35 KV

NOMINAL CURRENT

200 continuous Amp rms

Short current standing

10.000 symmetric Amp for 0, 17 sec

3,500 symmetric Amp for 3, 0 sec

VOLTAGE

Class 35 Kv

Maximal phase to ground voltage 21.1 Kv

Standing AC voltage 60 Hz during one minute 50 Kv

Standing DC voltage during 15 minutes 103 Kv

Impulse isolation level BIL and peak full wave 150 Kv

Minimum corona discharge voltage 26 Kv

Tap Changer

Continuous 100 Amp and 60 Amp

Voltage C15/25Kv

Impulse isolation level BIL and peak full wave 150 Kv

Standing AC voltage 60 Hz during one minute 50 Kv

Under NTC 3650 ICONTEC standard

Conformity certified by CIDET

Operation type: Circular

Cotizar este producto

Ver Ubicación